HVAC Load Calculator

Estimate the heating and cooling load (BTU/hr) for a room or building zone based on area, insulation, climate, occupancy, and internal gains.

Formulas Used

Envelope Conduction (sensible):
Qcond = U × A × ΔT   [BTU/hr]
Applied separately to net walls, ceiling, and windows. ΔT = |Toutdoor design − Tindoor|

Infiltration / Ventilation (sensible):
CFM = (ACH × Volume) / 60
Qinf = 0.018 × CFM × ΔT   [BTU/hr]
(0.018 = ρ·cp for air ≈ 0.075 lb/ft³ × 0.24 BTU/lb·°F × 60 min/hr)

Internal Gains (cooling only):
Qpeople = N × 250 BTU/hr (sensible, seated/light activity — ASHRAE 2017 HOF)
Qlighting = Watts × 3.412 BTU/W·hr
Qequipment = Watts × 3.412 × 0.70 (70% heat fraction to space)

Total Cooling Load: Qcool = Qcond,cool + Qinf,cool + Qinternal
Total Heating Load: Qheat = Qcond,heat + Qinf,heat (internal gains omitted — conservative)

Unit Conversions:
Tons of cooling = BTU/hr ÷ 12,000
kW of heating = BTU/hr ÷ 3,412.14

Equipment Sizing (ACCA Manual S):
Cooling equipment ≤ 1.15× calculated load  |  Heating equipment ≤ 1.25× calculated load

Assumptions & References